Temperature · IEC 60751

Pt100 calculator and resistance table

Convert temperature to RTD resistance or resistance to temperature for Pt100, Pt500 and Pt1000 sensors, from −200 °C to 850 °C.

Examples
Convert
Sensor
Advanced
Pt100 resistanceIEC 60751 · α = 0.00385

138.51 Ω

100.00 °C

Temperature
100.00 °C · 212.00 °F · 373.15 K
Resistance (Pt100)
138.506 Ω
Sensitivity
0.3793 Ω/°C
Class A tolerance
± 0.35 °C (± 0.133 Ω)

Working

  1. R = R₀ (1 + A·t + B·t²) = 100 × (1 + 0.39083 − 0.005775) = 138.506 Ω
  2. A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷, C = −4.183 × 10⁻¹² (t < 0 °C only), R₀ = 100 Ω

What the calculator is for

A platinum resistance thermometer changes resistance with temperature in a way IEC 60751 defines with the Callendar–Van Dusen equation. Use the calculator to check a sensor with a decade box or multimeter, set up a simulator, verify a transmitter, or find the temperature behind a resistance reading.

  • 0 °C to 850 °C: R = R₀ (1 + A·t + B·t²)
  • −200 °C to 0 °C: R = R₀ [1 + A·t + B·t² + C·(t − 100)·t³]
  • A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷, C = −4.183 × 10⁻¹²; R₀ = 100 Ω for a Pt100, 1,000 Ω for a Pt1000.

Worked example

At 100 °C a Pt100 reads 138.51 Ω and a Pt1000 1,385.06 Ω. Around room temperature a Pt100 changes by about 0.388 Ω per °C.

That small sensitivity is why wiring matters. In a 2-wire connection both leads add to the reading. Ten metres of 0.5 mm² copper is about 0.36 Ω per lead, so the reading is 0.72 Ω high and the temperature about 1.9 °C high. A 3-wire or 4-wire connection removes most or all of that error; with a Pt1000 the same leads cause a tenth of it.

Pt100 and Pt1000 resistance table

IEC 60751 resistance in ohms, every 10 °C
°CPt100 (Ω)Pt1000 (Ω)
−20018.52185.20
−19022.83228.25
−18027.10270.96
−17031.34313.35
−16035.54355.43
−15039.72397.23
−14043.88438.76
−13048.00480.05
−12052.11521.10
−11056.19561.93
−10060.26602.56
−9064.30643.00
−8068.33683.25
−7072.33723.35
−6076.33763.28
−5080.31803.06
−4084.27842.71
−3088.22882.22
−2092.16921.60
−1096.09960.86
0100.001,000.00
10103.901,039.03
20107.791,077.94
30111.671,116.73
40115.541,155.41
50119.401,193.97
60123.241,232.42
70127.081,270.75
80130.901,308.97
90134.711,347.07
100138.511,385.06
110142.291,422.93
120146.071,460.68
130149.831,498.32
140153.581,535.84
150157.331,573.25
160161.051,610.54
170164.771,647.72
180168.481,684.78
190172.171,721.73
200175.861,758.56
210179.531,795.28
220183.191,831.88
230186.841,868.36
240190.471,904.73
250194.101,940.98
260197.711,977.12
270201.312,013.14
280204.902,049.05
290208.482,084.84
300212.052,120.52
310215.612,156.08
320219.152,191.52
330222.682,226.85
340226.212,262.06
350229.722,297.16
360233.212,332.14
370236.702,367.01
380240.182,401.76
390243.642,436.40
400247.092,470.92
410250.532,505.33
420253.962,539.62
430257.382,573.79
440260.782,607.85
450264.182,641.79
460267.562,675.62
470270.932,709.33
480274.292,742.93
490277.642,776.41
500280.982,809.78
510284.302,843.03
520287.622,876.16
530290.922,909.18
540294.212,942.08
550297.492,974.87
560300.753,007.54
570304.013,040.10
580307.253,072.54
590310.493,104.87
600313.713,137.08
610316.923,169.18
620320.123,201.16
630323.303,233.02
640326.483,264.77
650329.643,296.40
660332.793,327.92
670335.933,359.32
680339.063,390.61
690342.183,421.78
700345.283,452.84
710348.383,483.78
720351.463,514.60
730354.533,545.31
740357.593,575.90
750360.643,606.38
760363.673,636.74
770366.703,666.99
780369.713,697.12
790372.713,727.14
800375.703,757.04
810378.683,786.83
820381.653,816.50
830384.603,846.05
840387.553,875.49
850390.483,904.81

Common mistakes

  • Using the linear 0.385 Ω/°C rule. It is exact only near 0 °C; at 300 °C the linear estimate is off by more than 5 °C.
  • Mixing α = 0.00385 and α = 0.00392 sensors. Older US sensors use a different curve. Check the sensor’s α before using this table.
  • Ignoring lead resistance. See the example above; select 2-wire under Advanced to see the error for your leads.
  • Reading the tolerance class as a system accuracy. Class A (± 0.15 + 0.002·|t| °C) covers the element only, not the transmitter, wiring or drift.

Basis

Coefficients and tolerance classes AA, A, B and C follow IEC 60751 for industrial platinum resistance thermometers (α = 0.00385 /°C). The inverse below 0 °C is solved numerically to better than 10⁻⁹ °C.

Frequently asked questions

What is the resistance of a Pt100 at 0 °C and 100 °C?

100.00 Ω at 0 °C and 138.51 Ω at 100 °C, by IEC 60751. A Pt1000 reads ten times as much: 1,000.00 Ω and 1,385.06 Ω.

How do I convert Pt100 resistance to temperature?

Above 100 Ω solve the quadratic R = R₀(1 + A·t + B·t²) for t. Below 100 Ω the equation includes the C term and is solved numerically; the calculator does both.

What is the difference between Pt100 and Pt1000?

Only the resistance at 0 °C: 100 Ω or 1,000 Ω. The Pt1000 has ten times the sensitivity in ohms, so lead resistance matters ten times less.

What does class A or class B mean?

IEC 60751 tolerance classes for the sensing element: class A is ± (0.15 + 0.002·|t|) °C and class B ± (0.3 + 0.005·|t|) °C.