Temperature · IEC 60584-1 · NIST ITS-90

Thermocouple calculator

Convert a thermocouple’s millivolts to temperature or temperature to millivolts, with the reference junction at any temperature.

Examples
Convert
°C

Where the thermocouple wires meet copper: 0 °C for the tables, or the terminal temperature for a meter reading.

Type K EMFNIST ITS-90 · IEC 60584-1

20.644 mV

at 500.0 °C, reference junction 0 °C

Hot junction
500.00 °C · 932.0 °F
EMF vs 0 °C reference
20.644 mV
Reference junction 0 °C
0.000 mV
EMF at the terminals
20.644 mV
Sensitivity (Seebeck)
42.6 µV/°C

Working

  1. E(500 °C) = Σ cᵢ·tⁱ + a₀·ea₁(t − a₂)² = 20.644 mV (reference junction at 0 °C)
  2. Type K reference function: NIST ITS-90 (IEC 60584-1), −270 to 1,372 °C

What the calculator is for

A thermocouple produces a voltage that depends on the temperature difference between its measuring (hot) junction and its reference (cold) junction, where the thermocouple wires meet copper. Tables give that voltage with the reference junction at 0 °C. In the field the reference junction is at the terminal temperature, so a reading has to be corrected before it means anything. Use the calculator to check a transmitter with a millivolt source, to read a thermocouple with a multimeter, or to look up a value.

  • Temperature → mV: measured EMF = E(t) − E(tref)
  • mV → temperature: E(t) = measured EMF + E(tref), then solve for t
  • E(t) is the NIST ITS-90 reference function for the type, the definition behind IEC 60584-1.

Worked example

A type K thermocouple at 500 °C produces 20.644 mV against a 0 °C reference. Now read a type K in the field with a multimeter: it shows 8.000 mV and the terminals are at 25 °C.

Looking 8.000 mV up in the table directly gives 196.5 °C, which is wrong. The terminals at 25 °C hide E(25 °C) = 1.000 mV, so the thermocouple’s full EMF is 8.000 + 1.000 = 9.000 mV, and the hot junction is at 221.5 °C. Simply adding 25 °C to the table answer only works where the curve is nearly straight.

Thermocouple reference table

EMF in mV, reference junction at 0 °C (NIST ITS-90), every 50 °C
°CKJTENRSB
−250−6.404—−6.180−9.718−4.313———
−200−5.891−7.890−5.603−8.825−3.990———
−150−4.913−6.500−4.648−7.279−3.336———
−100−3.554−4.633−3.379−5.237−2.407———
−50−1.889−2.431−1.819−2.787−1.269−0.226−0.236—
00.0000.0000.0000.0000.0000.0000.0000.000
502.0232.5852.0363.0481.3400.2960.2990.002
1004.0965.2694.2796.3192.7740.6470.6460.033
1506.1388.0106.7049.7894.3021.0411.0290.092
2008.13810.7799.28813.4215.9131.4691.4410.178
25010.15313.55512.01317.1817.5971.9231.8740.291
30012.20916.32714.86221.0369.3412.4012.3230.431
35014.29319.09017.81924.96411.1362.8962.7860.596
40016.39721.84820.87228.94612.9743.4083.2590.787
45018.51624.610—32.96514.8463.9333.7421.002
50020.64427.393—37.00516.7484.4714.2331.242
55022.77630.216—41.05318.6725.0214.7321.505
60024.90533.102—45.09320.6135.5835.2391.792
65027.02536.071—49.11622.5666.1575.7532.101
70029.12939.132—53.11224.5276.7436.2752.431
75031.21342.281—57.08026.4917.3406.8062.782
80033.27545.494—61.01728.4557.9507.3453.154
85035.31348.715—64.92230.4168.5717.8933.546
90037.32651.877—68.78732.3719.2058.4493.957
95039.31454.956—72.60334.3199.8509.0144.387
100041.27657.953—76.37336.25610.5069.5874.834
105043.21160.890——38.17911.17310.1685.299
110045.11963.792——40.08711.85010.7575.780
115046.99566.679——41.97612.53511.3516.276
120048.83869.553——43.84613.22811.9516.786
125050.644———45.69413.92612.5547.311
130052.410———47.51314.62913.1597.848
135054.138————15.33413.7668.397
1400—————16.04014.3738.956
1450—————16.74614.9789.524
1500—————17.45115.58210.099
1550—————18.15216.18210.679
1600—————18.84916.77711.263
1650—————19.54017.36611.848
1700—————20.22217.94712.433
1750—————20.87718.50313.014
1800———————13.591

Common mistakes

  • Ignoring the cold junction. The commonest error: a meter reading is the difference between two junctions, not the hot junction alone.
  • Copper wire in the run. Thermocouple or matching extension cable must run all the way to the reference junction; copper in between moves the reference point.
  • Reversed polarity. In IEC 60584-3 colours the negative leg is white. A reversed pair reads low and runs the wrong way as temperature rises.
  • Type B at low temperature. Its EMF is almost zero up to about 50 °C, so type B needs no cold-junction correction in practice but cannot measure low temperatures.

Basis

Reference functions and coefficients are those of NIST Monograph 175 (ITS-90), published in the NIST Temperature Scale Database SRD 60, and adopted in IEC 60584-1. Temperature from EMF is found by solving the reference function itself, not the approximate inverse polynomials, so both directions agree exactly. Every 10 °C value of the NIST tables is checked in SILProof’s tests.

Frequently asked questions

How do I convert thermocouple mV to temperature?

Add the EMF of the reference junction temperature to the measured mV, then find the temperature that gives that total EMF in the table or reference function for the thermocouple type.

What is cold-junction compensation?

The correction for the reference junction not being at 0 °C. Transmitters measure their terminal temperature and add its EMF to the measured voltage before converting.

What is the mV of a type K thermocouple at 100 °C?

4.096 mV with the reference junction at 0 °C, from the NIST ITS-90 tables.

Which thermocouple type should I use?

Type K is the general-purpose choice up to about 1,200 °C, type J for reducing atmospheres up to about 750 °C, type T for low temperatures, type N for better stability at high temperature, and R, S or B for very high temperatures.