SILProof / White papers / SIL verification checklist

White paper · SIL verification

What a good SIL verification contains

The 12 things every SIL verification report needs under IEC 61511 and IEC 61508, why each one matters, and the single line that can move the same SIF from SIL 2 to SIL 1.

Published 9 November 2026 · SILProof Engineering · ~16 minute read

A SIL verification report sheet with a checklist, three gate markers and a verified SIL stamp

Most SIL verifications look alike from the outside: a cover page, a PFDavg, a green “SIL 2 achieved”. The difference between a good one and a weak one is invisible until someone asks a simple question. Where did this failure rate come from? What does your proof test actually test? What happens when the valve fails partially? A good SIL verification has already answered every one of those questions, in writing, before anyone asks.

Definition

A SIL verification is the documented demonstration that a safety instrumented function (SIF), as designed and as it will be tested and maintained, achieves its target Safety Integrity Level on all three requirements: probabilistic performance (PFDavg or PFH), architectural constraints and systematic capability. The verified SIL is the lowest of the three.

This paper is the checklist we wish every project had. It is written for engineers doing their first SIL calculation and for reviewers who sign them off. Each item says what belongs in the report, why it matters, and the question a reviewer will ask.

The checklist at a glance

  1. SIF definition and safe state
  2. Target SIL, demand mode and its source
  3. Architecture as installed
  4. Credible, traceable failure data
  5. Proof test interval and coverage
  6. Mission time and overhaul
  7. Common cause (β factor)
  8. Diagnostics and repair time
  9. The PFDavg or PFH calculation
  10. Architectural constraints (HFT)
  11. Systematic capability
  12. Verdict, margin and hand-over
INPUTSTHE THREE GATESVERDICT 1SIF definition and target SIL 2Architecture as installed 3Traceable failure data 4Proof test and coverage 5Common cause (β) 6Diagnostics and repair time GATE 1Probabilistic performancePFDavg or PFH GATE 2Architectural constraintsHFT · Table 6 · Route 1H/2H GATE 3Systematic capabilitySC certificate or prior use VERIFIED SIL Lowest of thethree gates plus margin and which gatelimited the claim HANDED TO OPERATIONS · Proof test interval· Test procedure and coverage· Bypass and repair limits· Field data to collect If an input changes in the plant, the verification has to change with it.
Figure 1. Anatomy of a SIL verification. Six inputs feed three gates; the lowest gate sets the verified SIL, and the assumptions become operating requirements.

1. Start with the function, not the hardware

A SIL belongs to a safety function, not to a transmitter or a valve. So a verification that opens with a device list has already started in the wrong place.

01SIF definition and safe state

One sentence that anyone on the plant can read: what is detected, what decides, what acts, and what the safe state is. For example: “High pressure in V-101 (PT-101 above 18 barg) closes inlet valve XV-101 within 5 seconds.” Add the tags, the trip set point, the process safety time and the required response time.

The response time matters more than it looks. If the valve takes 12 seconds to close and the process safety time is 10 seconds, no amount of redundancy rescues the function.

Reviewer asks: Does the response time of the whole loop, sensor to closed valve, fit inside the process safety time?

02Target SIL, demand mode and its source

The target must trace back to the risk analysis that set it, a LOPA or risk graph, and to the Safety Requirements Specification (SRS). This is the line between SIL determination, which sets the target, and SIL verification, which proves it is met.

State the demand mode and justify it. Low demand mode means the function is demanded no more than once a year; above that, or where the SIF acts continuously, the measure becomes PFH (average frequency of dangerous failure per hour) instead of PFDavg. Getting the mode wrong means calculating the wrong quantity.

Reviewer asks: Which hazard scenario and which risk analysis revision does this target come from? Is the expected demand rate consistent with low demand mode?

2. The inputs that make or break the number

A SIL calculation is only as good as its inputs. These six items are where most verifications are quietly optimistic.

03Architecture as installed

List every element in the path from process to safe state, grouped into sensor, logic solver and final element subsystems, with the voting of each (1oo1, 1oo2, 2oo3 and so on). Include the parts that are easy to forget: isolating barriers, I/O cards, interposing relays, the solenoid valve, the actuator and the valve itself.

A common shortcut models the final element as “the valve”. In reality the solenoid and actuator often contribute as much as the valve body. Leave them out and the PFDavg looks better than the plant will ever be.

Reviewer asks: Does the model match the P&ID and loop drawings, including what is shared between channels (process connection, power supply, air supply)?

04Credible, traceable failure data

For every device: the dangerous undetected rate (λDU), dangerous detected rate (λDD), safe failure rate and the source of each. IEC 61511-1 expects the reliability data to be credible, traceable, documented and justified, which in practice means one of three sources: a manufacturer’s FMEDA or certificate, a recognised industry database, or your own plant’s field data.

Then check that the data fits the service. A transmitter rated for clean gas will not achieve the same failure rate on a plugging slurry. A certificate’s λDU often assumes conditions your process does not provide. See the failure data knowledge note for how to choose and justify sources.

Reviewer asks: Can I find each number in a named document? Is it appropriate for this process fluid, environment and maintenance quality?

05Proof test interval and coverage

The proof test interval (T1) is how often the function is tested. The proof test coverage (PTC) is the fraction of dangerous undetected failures that test actually reveals. Both must link to a real, written test procedure, not to an aspiration.

A partial stroke test does not prove tight shut-off. A transmitter test that injects a signal at the card does not prove the impulse line is clear. Each limitation lowers the coverage, and the worked example below shows how much that costs. The proof testing note covers how to estimate coverage honestly.

Reviewer asks: Which procedure delivers this coverage? Does the interval match the maintenance plan and the turnaround schedule?

06Mission time and overhaul

Failures the proof test cannot find do not disappear. They stay latent until the device is overhauled, replaced or retired. That period, the mission time or overhaul interval, must be stated, because the untested fraction of λDU accumulates over it rather than over one test interval.

A verification that claims 90% coverage without saying when the other 10% is found has hidden one of its most important assumptions.

Reviewer asks: When is the untested part of each device fully restored: at a 6-year overhaul, a 10-year replacement, or never?

07Common cause (β factor)

Redundancy only helps if channels fail independently. The β factor is the fraction of failures that hit all channels at once: the same plugged tapping, the same miscalibration by the same technician, the same contaminated air supply. State β (and βD for detected failures) for every redundant group and say how it was chosen, typically with the IEC 61508-6 scoring method.

For redundant architectures β often dominates the result. Our Markov paper shows a 2oo3 group where β = 5% makes PFDavg 48.5 times worse than the “independent channels” answer.

Reviewer asks: What separation, diversity and test practice justify this β? Is it the same number on every SIF, regardless of design?

08Diagnostics, detected-fault response and repair time

Diagnostics only reduce risk if something happens when they detect a fault. State the diagnostic coverage, what a detected fault does (trip to safe state, or alarm and degrade the voting) and the repair time assumed (MTTR, or mean repair time MRT for failures found by proof test).

An 8-hour MTTR on an offshore platform that needs a helicopter for spares is not an assumption; it is a hope. If the plant runs on with a channel failed, the verification must say how long that is allowed and what compensating measures apply.

Reviewer asks: Is the repair time realistic for this site, and is the maximum time in degraded mode written into the operating procedures?

3. Worked example: one line, two different SILs

Take a simple low-demand SIF with target SIL 2: one pressure transmitter, a certified safety PLC and one shutdown valve assembly. The data is typical:

SubsystemInputValue
Sensor (1oo1)λDU of the pressure transmitter1.0 × 10−7 per hour
Logic solverPFDavg from the manufacturer’s safety manual1.0 × 10−5
Final element (1oo1)λDU of solenoid, actuator and valve together1.5 × 10−6 per hour
AllProof test interval; untested failures found at overhaul1 year; every 10 years

With perfect proof testing, the simplified 1oo1 equation PFDavg ≈ λDU · T1 / 2 gives a total of 7.02 × 10−3: RRF 142, inside the SIL 2 band. Figure 2 shows where that number comes from.

Where the PFDavg comes from (proof test coverage 100%) Final element · 93.6% Transmitter · 6.2% Logic solver · 0.1% Solenoid, actuator and valve · 93.6% Total PFDavg 7.02 × 10⁻3 · RRF 142 · SIL 2 band
Figure 2. In the base case, the final element is 94% of the PFDavg. This is typical: the valve assembly, not the transmitter or the PLC, usually decides the result.

Now apply the one line most reports skip: proof test coverage of the final element. With imperfect coverage, the equation gains a second term for failures found only at overhaul: PFDavg ≈ PTC · λDU · T1 / 2 + (1 − PTC) · λDU · Toverhaul / 2.

Final element PTCFinal element PFDavgSIF PFDavgRRFVerified (Gate 1)
100%6.57 × 10−37.02 × 10−3142SIL 2
95%9.53 × 10−39.97 × 10−3100SIL 2
90%1.25 × 10−21.29 × 10−277SIL 1
70%2.43 × 10−22.48 × 10−240SIL 1

Same transmitter, same PLC, same valve. A proof test that misses one failure in ten turns a SIL 2 function into a SIL 1 function.

At 95% coverage the function passes with RRF 100: technically SIL 2, with no margin at all. A good verification shows this sensitivity openly instead of reporting only the best case. You can reproduce these numbers in the PFD calculator.

4. The calculation itself

09The PFDavg or PFH calculation

State the method and its source: the simplified equations of IEC 61508-6 Annex B, a fault tree, a Markov model or a reliability block diagram. Show the result for each subsystem, not just the total, so a reader can see which part dominates and where improvement pays off.

The method must match the architecture. Simplified equations are excellent for standard voting with modest failure rates; staggered testing, complex repair strategies or large λ·T values may need a Markov model. Whichever you use, a second person should be able to reproduce the number from the report alone. That is why SILProof publishes its engine validation against IEC reference cases.

Reviewer asks: Could I recompute this from the report? Do the units, intervals and time bases agree across subsystems?

For background on the equations and what moves the result, see the PFDavg knowledge note.

5. Architecture and systematic capability

A PFDavg in the SIL 2 band does not make a function SIL 2. Two more gates have to pass, as explained in The Three Gates to SIL.

10Architectural constraints (hardware fault tolerance)

Check each subsystem’s hardware fault tolerance (HFT) against the minimum required. Under IEC 61511-1 Edition 2 that is Table 6: HFT 0 for SIL 1, and for SIL 2 in low demand mode; HFT 1 for SIL 2 in high demand or continuous mode and for SIL 3. Under IEC 61508 the equivalent is Route 1H, using safe failure fraction, or Route 2H, using field-proven data.

State which route you used and why. Mixing routes inside one subsystem without saying so is one of the most common findings in a functional safety assessment.

Reviewer asks: Which table or route applies, and does every subsystem meet it on its own?

11Systematic capability

Random failures are only half the story. Systematic failures come from specification errors, software bugs, wrong configuration and poor modification control, and no failure rate can average them away. For each device, record its systematic capability (SC) from an IEC 61508 certificate, or a prior-use justification under IEC 61511-1 Clause 11.5 based on documented operating experience in a similar environment.

Include the application program: the logic in the safety PLC is part of the function and needs its own development and testing evidence.

Reviewer asks: Does each device’s SC (or prior-use evidence) reach the target SIL, and are the safety manual’s conditions of use actually met in this installation?

6. The verdict and the hand-over

12Verdict, margin and hand-over to operations

The conclusion of a good SIL verification fits in one table: the result of each gate, the verified SIL (the lowest of the three), the margin against the target, and which gate limited the claim. Add the sensitivities that matter, such as the effect of a longer test interval or a higher β.

Then hand over the assumptions. Every number used becomes an obligation for operations: the proof test interval, the test procedure and the coverage it must deliver, bypass limits, maximum repair time, and the field data to collect so the failure rates can be checked later. These belong in the SRS and the maintenance system, not only in the report.

Finally: a revision number, the author, an independent reviewer, and the date. A verification is a living document; when an assumption changes in the plant, the verification must change with it.

Reviewer asks: If I gave only this page to the operations team, would they know exactly what they must do to keep the SIL?

7. Red flags reviewers look for

  • A single number on the cover and no subsystem breakdown.
  • Failure rates without a source, or certificate data used outside its stated conditions.
  • 100% proof test coverage assumed for valves, with no mention of what the test cannot detect.
  • A proof test interval that differs from the maintenance plan or the turnaround cycle.
  • The final element modelled as “valve”, without solenoid and actuator.
  • β not stated, or the same β on every SIF regardless of design.
  • “SIL 2 achieved” from PFDavg alone, with no HFT or systematic capability check.
  • No revision, no reviewer, and no link back to the SRS or the hazard it protects against.
Engineering takeaway: a good SIL verification is not the one with the best number. It is the one where every number has a source, every assumption becomes an operating requirement, and the verified SIL is the lowest of the three gates, stated with its margin.

8. Frequently asked questions

What is SIL verification?

SIL verification is the documented demonstration that a safety instrumented function, as designed and as it will be tested and maintained, achieves its target Safety Integrity Level. It must pass three requirements: probabilistic performance (PFDavg or PFH), architectural constraints (hardware fault tolerance) and systematic capability. The verified SIL is the lowest of the three.

What should a SIL verification report include?

A good report states the SIF and its target SIL, the architecture as installed, the source of every failure rate, the proof test interval and coverage, mission time, common cause (β), diagnostics and repair time, the PFDavg or PFH calculation per subsystem, the hardware fault tolerance check, systematic capability evidence, the governing SIL with its margin, and the assumptions handed to operations.

What is the difference between SIL determination and SIL verification?

SIL determination (also called SIL assessment or SIL allocation) uses risk analysis such as LOPA or a risk graph to set the target SIL a function needs. SIL verification comes later and proves that the designed function actually achieves that target.

Is a PFDavg calculation enough to verify a SIL?

No. PFDavg (or PFH for high-demand and continuous mode) is only the probabilistic part. IEC 61511 also requires the architecture to meet the minimum hardware fault tolerance and every device to have adequate systematic capability or prior-use justification.

How does proof test coverage affect PFDavg?

Failures that a proof test cannot reveal stay hidden until a full overhaul or the end of the mission time, so they accumulate far longer than one test interval. In the worked example, dropping final element proof test coverage from 100% to 90% moves the same SIF from SIL 2 to SIL 1.

When must a SIL verification be updated?

Whenever an assumption changes: a modified design, a different device, a longer proof test interval, a less thorough test procedure, or field failure data that is worse than the data used. A verification describes the function as it is operated, not only as it was designed.

Primary and technical references
  1. IEC 61511-1:2016: functional safety, safety instrumented systems for the process industry sector (Clause 11, including Table 6 and device selection).
  2. IEC 61508-2:2010: requirements for E/E/PE safety-related systems, including Routes 1H and 2H.
  3. IEC 61508-6:2010, Annex B: simplified equations for PFDavg and PFH; Annex D: β-factor estimation.
  4. UK HSE: Control systems: integrity levels and architectural considerations.
  5. SILProof: The Three Gates to SIL: companion white paper.
About this white paper
Written for engineers preparing their first SIL verification and for the reviewers who sign them off. The worked example uses simplified equations and illustrative data. Educational support, not a certificate, assessment or substitute for competent project review.